Frequently tripping of generation plant for percentage differential protection
##plugins.themes.bootstrap3.article.main##
Abstract
INTRODUCTION. This article discussed the incorrect operation of differential protections used in electric generators due to inrush of the power transformers. OBJECTIVE. Find an economical solution to the wrong operations of protections. METHOD. Using mathematical simulation including in this the result of testing the primary protections devices faced the problem. RESULTS. Changing some settings of the percentage differential functions solves the problem caused by incorrect selection of current transformers. DISCUSSION AND CONCLUSIONS. The differential percentage function has its most sensitive and vulnerable point to inrush currents in low current areas. Inrush current block function does not eliminate incorrect operation of differential protections on multi – generators schemes connected to a single bar. It is necessary to select current transformers with similar magnetic characteristic for use in generator differential protection.
##plugins.themes.bootstrap3.article.details##

This work is licensed under a Creative Commons Attribution 4.0 International License.
The articles are licensed under a Creative Commons CC BY 4.0 open access licence, which means that anyone can download and read the article free of charge. In addition, the article may be reused and cited as long as the original published version is cited. These conditions allow for maximum use and exposure of the work, while ensuring that the authors receive proper credit.